Characteristics | |
---|---|
Operation speed | 0.01mm-1m/sec |
Operating frequency | Mechanical: 240 operations/min. Electrical: 20 operations/min. |
Contact resistance | 15mΩ max. (initial value) |
Dielectric strength | 1000VAC, 50/60 Hz for 1 minute between terminals of the same polarity |
1500VAC, 50/60 HZ for 1 minute between current-carrying and non-current- carrying metal parts | |
1500VAC, 50/60 HZ for 1 minute between each terminal and ground | |
Vibration | 10-55Hz, 1.5mm double amplitude |
Humidity | General purpose type: 85% RH max., Sealed type: 95% RH max. |
Life | Mechanical: 1 Million Electrical: 0.5 Million |
Warranty | 24 Months* |
Utilization Category for Limit Switches | ||
---|---|---|
Kind of Current | Category | Typical Application |
Alternative Current | AC-15 | Control of Electromagnetic Load > 72 VA |
Direct Current | DC-13 | Control of Electromagnets |
Contact Rating Designation Based on Utilization Catagories | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Designation | Utilization Catagory | Conventional Enclosed Thermal Current | Rated Operational Current (A) at Rated Operational Voltage | VA Ratings | ||||||
Resistance Load | 120 V | 240 V | 380 V | 480 V | 500 V | 600 V | Make | Break | ||
AC-15 | 10 | 6 | 3 | - | - | - | - | - | 7200 | 720 |
Direct Current | 125V | 250 V | 400 V | 500 V | 600 V | Make | Break | |||
P600 | DC-13 | 5 | 1.1 | 0.55 | 0.31 | 0.27 | 0.2 | 138 | 138 |